National Instruments Direct Injector Driver System Manual
© 2013 National Instruments. All rights reserved.
If the green and amber LEDs directly under the controller Ethernet port are not active or blinking, then there
is no physical connection to a network router or PC, or there is no power to the controller. Please diagnose
the Ethernet cable connection or controller power problem.
If none of the above suggestions resolve the system connection problem, follow the
instructions below to reset the system controller network interface settings to DHCP.
cRIO-9076 Controller
To manually reset the network settings of the cRIO-9076 controller included with 3-channel DI Driver Systems, follow
the steps below:
1. Power up the cRIO-9076 controller.
2. Press and hold the
reset
button for greater than 5 seconds. Release the
reset
button. This will cause the
controller to reboot into safe mode and the DI Driver System software will not load. This is indicated by the amber
Status
LED blinking 3 times.
3. Again, press and hold the
reset
button for greater than 5 seconds (while booted into safe mode). Release the
reset button. This will cause the controller to reboot into safe mode
AND
reset the network interface settings to
DHCP mode.
4. Press and immediately release the
reset
button. This will cause the controller to reboot normally and start the DI
Driver System software. Wait about 1 minute for both the
USER1
and
USER FPGA
LEDs to start blinking.
cRIO-9022 Controller
To manually reset the network settings of the cRIO-9022 controller included with 6-, 9-, and 12-channel DI Driver
Systems, follow the steps below:
1. Power up the cRIO-9022 controller.
2. Switch the
IP RESET
switch to
ON
.
3. Press and immediately release the
reset
button. This will cause the controller to reboot normally and start the DI
Driver System software. However, the network settings will be reset to DHCP mode. Wait about 1 minute for both
the
USER1
and
USER FPGA
LEDs to start blinking.
4. Switch the
IP RESET
switch to
OFF
.