FP0 Hardware
Self-Diagnostic and Troubleshooting
11-12
Matsushita Electric Works (Europe) AG
Description and steps to take
Operation
status
Name of error
Error
code
E8
Operand error
(OPR COMBI)
Stops
There is an incorrect operand in an instruction which requires a
specific combination operands (for example, the operands must all be
of a certain type).
Enter the correct combination of operands.
11.3.3
Self-Diagnostic Error Codes
Error
code
Name of error
Operation
status
Description and steps to take
E31
Interrupt error 1
Stops
An interrupt occurred without an interrupt request.
A hardware problem or error due to noise is possible.
Turn OFF the power and check the noise conditions.
E32
Interrupt error 2
Stops
An interrupt occurred without an interrupt request.
A hardware problem or error due to noise is possible.
Turn OFF the power and check the noise conditions.
There is no interrupt program for an interrupt which occurred.
Check the number of the interrupt program and change it to agree
with the interrupt request.
E45
Operation error
Selects
Operation became impossible during a high-level instruction. The
cause of the operation error varies depending on the instruction. In
system register 26, select “1: Continue operation” or “0: Stop”
E100
to
E199
Self-diagnostic
error set by
F148 (ERR)
Stops
The error set using high-level instruction F148(ERR) has occurred.
Clear the error based on the set detection conditions
E200
to
E299
F148 (ERR)
instruction
Continues
Summary of Contents for FP Series
Page 12: ...Chapter 1 Overview...
Page 21: ...FP0 Hardware Overview 1 10 Matsushita Electric Works Europe AG...
Page 22: ...Chapter 2 Control Units...
Page 44: ...Chapter 3 Expansion I O Units...
Page 67: ...FP0 Hardware Expansion I O Units 3 24 Matsushita Electric Works Europe AG...
Page 68: ...Chapter 4 Analog I O Unit...
Page 87: ...FP0 Hardware Analog I O Unit 4 20 Matsushita Electric Works Europe AG...
Page 88: ...Chapter 5 FP0 I O Link Unit MEWNET F...
Page 102: ...Chapter 6 Power Supply Unit...
Page 105: ...FP0 Hardware Power Supply Unit 6 4 Matsushita Electric Works Europe AG...
Page 106: ...Chapter 7 I O Allocation...
Page 112: ...Chapter 8 Installation...
Page 122: ...Chapter 9 Wiring...
Page 139: ...FP0 Hardware Wiring 9 18 Matsushita Electric Works Europe AG...
Page 140: ...Chapter 10 Trial Operation...
Page 143: ...FP0 Hardware Trial Operation 10 4 Matsushita Electric Works Europe AG...
Page 144: ...Chapter 11 Self Diagnostic and Troubleshooting...
Page 156: ...Appendix A System Registers...
Page 170: ...Appendix B Special Internal Relays...
Page 174: ...Appendix C Special Data Registers...
Page 183: ...FP0 Hardware Special Data Registers C 10 Matsushita Electric Works Europe AG...
Page 184: ...Appendix D Dimensions...
Page 195: ...FP0 Hardware Dimensions D 12 Matsushita Electric Works Europe AG...