![NAiS FP Series Hardware Manual Download Page 147](http://html1.mh-extra.com/html/nais/fp-series/fp-series_hardware-manual_3130586147.webp)
FP0 Hardware
Self-Diagnostic and Troubleshooting
11-4
Matsushita Electric Works (Europe) AG
Error code is 20 or higher
A self-diagnostic error other than a syntax error has occurred.
<Condition>
Follow the procedures described in the table of error codes (
Use the programming tool in PROG. mode to clear the error.
Using NPST-GR software
Press the <F3> key in the status display menu described on the previous
page. Error code 43 and higher can be cleared.
Using FPWIN GR
Click the “Clear Error” button in the status display menu described on the pre-
vious page.
Using FP programmer
II
Press the keys as shown on the right.
Error code 43 and higher can be cleared.
Using FPWIN Pro
Monitor –> PLC Status –> Click Clear
D
In the PROG. mode, the power supply can be turned OFF and then ON
again to clear the error, but all of the contents of the operation memory
except hold type data are cleared.
D
An error can also be cleared by executing a self-diagnostic error set
instruction F148 (ERR).
<Procedure 1 >
<Procedure 2>
2
ACLR
OP
(–)
1
1
SC
SHIFT
INST
(DELT)
ENT
Note
When an operation error (error code 45) occurs, the address at
which the error occurred is stored in special data registers
DT9017 and DT9018. If this happens, monitor the address at
which the error occurred before cancelling the error.
Summary of Contents for FP Series
Page 12: ...Chapter 1 Overview...
Page 21: ...FP0 Hardware Overview 1 10 Matsushita Electric Works Europe AG...
Page 22: ...Chapter 2 Control Units...
Page 44: ...Chapter 3 Expansion I O Units...
Page 67: ...FP0 Hardware Expansion I O Units 3 24 Matsushita Electric Works Europe AG...
Page 68: ...Chapter 4 Analog I O Unit...
Page 87: ...FP0 Hardware Analog I O Unit 4 20 Matsushita Electric Works Europe AG...
Page 88: ...Chapter 5 FP0 I O Link Unit MEWNET F...
Page 102: ...Chapter 6 Power Supply Unit...
Page 105: ...FP0 Hardware Power Supply Unit 6 4 Matsushita Electric Works Europe AG...
Page 106: ...Chapter 7 I O Allocation...
Page 112: ...Chapter 8 Installation...
Page 122: ...Chapter 9 Wiring...
Page 139: ...FP0 Hardware Wiring 9 18 Matsushita Electric Works Europe AG...
Page 140: ...Chapter 10 Trial Operation...
Page 143: ...FP0 Hardware Trial Operation 10 4 Matsushita Electric Works Europe AG...
Page 144: ...Chapter 11 Self Diagnostic and Troubleshooting...
Page 156: ...Appendix A System Registers...
Page 170: ...Appendix B Special Internal Relays...
Page 174: ...Appendix C Special Data Registers...
Page 183: ...FP0 Hardware Special Data Registers C 10 Matsushita Electric Works Europe AG...
Page 184: ...Appendix D Dimensions...
Page 195: ...FP0 Hardware Dimensions D 12 Matsushita Electric Works Europe AG...