Protection Relay Settings
25
Protection Relay Settings
The myPV ClearSky™ Interconnection is designed to provide a set of features that
support witness testing requirements, maintenance modes, and protection
requirements.
Template Relay Settings File
The SEL-751 Protection Relay, and the myPV ClearSky’s intended operational
behaviors rely on logic programmed into the relay’s RDB settings file.
Solar-Ops provides template RDB files that should be used as a starting point for any
Customer specific protection elements, or reclosing behaviors.
Template RDB files are available for download under the
webpage.
ClearSky RDB template files include:
1. Repair Service vs. Automatic Mode
2. Power Supply & UPS Battery TRIP
3. Single Phase TRIP Support
ClearSky RDB template files require customer settings to support:
1. Interconnection protection element assignment and settings are required to be
programmed by the Customer
2. Interconnection reclosing behavior settings are required to be programmed by the
Customer
Repair Service vs. Automatic Mode
The myPV ClearSky’s Mode Selector Switch provides Technician’s a simple means to
DISABLE the Protective Relay’s ability to CLOSE.
Summary of Contents for ClearSky
Page 1: ...myPV ClearSky User Manual 1 myPV ClearSky User Manual ...
Page 12: ...Resources 12 ...
Page 14: ...Resources 14 ...
Page 19: ...Resources 19 ...
Page 20: ...Resources 20 ...
Page 48: ...Pre Energization Checks 48 Control Panel Verification Locations ...
Page 55: ...Initial Energization 55 ...
Page 63: ...Operational Testing 63 The myPV ClearSky may be left in this condition indefinitely ...
Page 68: ...Spare Parts 68 ...
Page 69: ...Spare Parts 69 ...