Operational Testing
61
MODE.
Single Phase Test Operation:
1. Press and Hold the SPD-TEST button for approximately 5 seconds, until …
2. … the ENABLED Yellow indicator is illuminated
3. Firmly press the A-PHASE button to TRIP the MV VFI Breaker for phase A … the
breaker should TRIP / OPEN
4. The A-PHASE button’s TRIPPED Green indicator should now be illuminated
5. The CLOSE button’s BREAKER CLOSED Red indicator will remain illuminated so
long as any-one MV VFI Breaker is still in the CLOSED position
Numbered Illustration of Protective Relay Indicators
Additional notes on single-phase mode operation: