Section 50
00-02-0329
01-09-07 -
37 -
Setup A – Output Mode
Upon Shutdown, the FV- (Fuel Valve minus) and the
IGN SHDN (Ignition Shutdown) terminals change state
and either conduct-to-ground or open-to-ground. The
change of state depends on the configuration of SETUP
A.
There are four choices, terminals are shown in shutdown
state:
Setting
FV -
IGN SHDN
0 Closed Closed
1 Open Open
2 Open Closed
3 Closed Open
Table Note: Closed indicates a closed to ground state and
open indicates an open to ground state when the TTD unit is
in Shutdown Mode.
Use the [UP ARROW] or [DOWN ARROW] key to
select the Output Mode setting. Press [ENTER] to save
the setting.