152054 – SCR Fault Odd
Red alarm. Initiated by IC922.
Cause
Corrective action
Hardware not ready for
operation.
u
Restart ignition system.
152055 – SCR Fault Even
Red alarm. Initiated by IC922.
Cause
Corrective action
Hardware not ready for
operation.
u
Restart ignition system.
152056 – Odd Energy Level out of Range
Yellow alarm. Initiated by IC922.
Cause
Corrective action
Specified energy level is beyond
the valid range.
u
Adjust value.
152057 – Even Energy Level out of Range
Yellow alarm. Initiated by IC922.
Cause
Corrective action
Specified energy level is beyond
the valid range.
u
Adjust value.
153101 – Error Status
Red alarm. Initiated by antiknock control.
Cause
Corrective action
AKR combined alarm. At least
one additional AKR alarm is
pending.
u
Rectify the cause of the source alarm.
153102 – Combined Error
Red alarm. Initiated by antiknock control.
Cause
Corrective action
Combined alarm (for details,
refer to the source alarm).
u
Combined alarm (for details, refer to the source alarm).
153103 – Internal Error
Red alarm. Initiated by antiknock control.
Cause
Corrective action
Hardware not ready for
operation.
u
Restart antiknock control system.