Operation
3.6
Stopping the engine in manual mode
Preconditions
• Generator is not connected to network.
• Engine is running in manual mode.
CAUTION
Stopping the engine when it is running at full load causes extreme stress to the engine.
Risk of overheating, damage to components!
• Before stopping the engine, operate it at idle speed until operating temperatures decrease
and stable values are indicated.
Preparation
Item
Task
Engine
After the generator circuit breaker has been opened, allow the engine to
cool down by running it idle for approx. 5 minutes.
Stopping the engine
Item
Task
Switching cabinet, control panel etc.
(depending on manufacturer)
Press stop button.
• Automatic stopping procedure is performed;
• Engine is stopped.
After stopping the engine
Item
Task
Cooling pump
Operate for approx. 5 minutes after engine stop.