365 – AL Stop SV Ground Wiring
Cause
Corrective action
Short circuit of injector positive
connection to ground of one or
more injectors.
Short circuit of negative injector
connection or of one or more
injectors to ground.
1. Check wiring (→ Page 160).
2. Restart engine.
3. Contact Service.
415 – LO P-Coolant Charge-Air Cooler
Cause
Corrective action
The charge-air coolant pressure
in the charge-air cooler at
sensor B43 has undershot limit
value 1. Charge-air coolant
pressure is too low.
1. Check relief bore on charge-air coolant pump (→ Page 154)-
2. Check charge-air cooler for coolant discharge (→ Page 115).
3. Contact Service.
416 – SSO P-Coolant Charge-Air Cooler
Cause
Corrective action
The charge-air coolant pressure
in the charge-air cooler at
sensor B43 has undershot limit
value 2. Charge-air coolant
pressure is too low.
1. Check relief bore on charge-air coolant pump (→ Page 154)-
2. Check charge-air cooler for coolant discharge (→ Page 115).
3. Contact Service.
440 – AL L1 P-Aux1
Cause
Corrective action
The pressure measurement
sensor at the pressure
measurement channel has
undershot limit value 1. The
pressure value at the pressure
measurement channel is too
low.
u
Contact Service.
442 – AL- L2 P-Aux1
Cause
Corrective action
The pressure measurement
sensor at the pressure
measurement channel has
undershot limit value 2. The
pressure value at the pressure
measurement channel is too
low.
u
Contact Service.