
7.21.2 Fuel treatment system – Switching on
Preconditions
☑
The on-board power supply is switched on.
NOTICE
Risk of damage to engine/system.
Risk of severe damage to property!
• Before switching on, ensure that the engine/system is ready for operation.
• Before switching on, ensure that all housings are closed.
• Before switching on, ensure that no work is in progress anywhere on the entire system.
Fuel treatment system – Switching on
1.
Carry out checks prior to start-up (→ Page 139).
2.
Switch on master switch on switchgear cabinet.
Result:
Signal lamp “Control voltage present” lights up.
3.
Switch on switch for pump.
Result:
Signal lamp “Pump running” lights up.
140 | Fuel Treatment System | MS150119/01E 2016-02
TIM-ID: 0000007731 - 006