Appendix
The data in this manual are not binding and may be changed by the manufacturer without notice.
Reproduction of this manual, even partial, is strictly prohibited.
H
YDRAULIC
CIRCUIT
CHECK
LIST
(
ONLY
CY
UNITS
)
No
No
No
No
No
No
No
Si
Si
Si
Si
Si
Si
Si
Hydraulic circuit connections made in
compliance with best technical practice?
Water inlet and outlet connections follow
correct direction?
Unit is full of water and all air pockets have
been removed?
Water flow rate to evaporator is as prescribed
in the manual?
Any flow switches installed enabled and
correctly connected?
Water filter upstream from evaporator
installed correctly?
Water filter upstream from condenser installed
correctly?
Water connections have been made correctly
Adapt the connections
Correct connections
Fill hydraulic circuit and/or bleed the air
if present
Adjust water flow rate
Connect correctly or renew the
component
Repair or renew the filter
Repair or renew the filter
Pump direction of rotation correct?
Restore correct direction of rotation
Start
No
No
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes