OPERATING AND MAINTENANCE MANUAL
Installation
MCCY - CY 013÷301
27
ENGLISH
EN
The data in this manual are not binding and they can be modified by the manufacturer without notice.
Reproduction of this manual is strictly prohibited.
5.8.1
Installation and routing of refrigerant lines for condensing units
During installation and commissioning take the following points into consideration:
1. First of all consider the refrigerant lines to connect the MCCY unit with the evaporator section. To limit loss of
cooling capacity ensure that the refrigerant lines are as short as possible and reduce the number of bends to a
minimum, avoiding possible flow restrictions caused by excessively tight bends. It is essential to comply with the
maximum equivalent lengths and maximum level differences shown in the following table:
On the back site of the MCCY 081÷301 units there are refrigerant connections (see figure above) that have to be welded,
the dimensions of their diameter are indicated in the table below.
MCCY
Unit
Suction line
diameter
[mm]
Liquid line diameter
[mm]
Maximum distance
between MCCY
units and
motoevaporant units
[m]
Maximum unit level
difference
[m]
MCCY 013
12
8
20
9
MCCY 015
16
8
20
9
MCCY 020
16
10
20
9
MCCY 031
18
10
30
13,5
MCCY 051
22
12
30
13,5
MCCY 071
22
12
30
13,5
MCCY 081
28
16
30
13,5
MCCY 101
28
16
30
13,5
MCCY 131
35
18
30
13,5
MCCY 171
35
18
30
13,5
MCCY 211
35
22
30
13,5
MCCY 251
35
22
30
13,5
MCCY 301
35
22
30
13,5
REFRIGERANT
REFRIGERANT
INLET
OUTLET