OPERATING AND MAINTENANCE MANUAL
Electronic Board
MCCY - CY 013÷301
44
ENGLISH
EN
The data in this manual are not binding and they can be modified by the manufacturer without notice.
Reproduction of this manual is strictly prohibited.
CF28
It allows to select the operating modality (chiller / heat pump) by keyboard or by digital / analogue input:
•
0= Selection by keyboard which has the priority on the digital / analogue input.
•
1= Selection by digital input. The selection is enabled if a digital input is configured as 4
(remote chiller / heat pump). If the polarity of the digital input is 0: the “opened” status forces
the unit to chiller operation, the “closed” status to heat pump operation. If the polarity of the
digital input is 1: the “opened” status forces the unit to heat pump operation, the “closed” status
to chiller operation. If no digital input has been configured to 4, the unit remains in stand-by.
The selection to chiller or heat pump by keyboard is disabled. It is possible to switch on or off
the unit by keyboard only during the selected operating modality.
•
2= Selection by analogue input, it has the priority on the digital input. In the event of external
air temperatures included in the differential CF30, it is possible to change the operating
modality by keyboard.
Both with
CF28
=1 and
CF28
=2, if the unit is operating as chiller or as heat pump and the modification of the
operating modality is required, the controller stops all the outlets and wait for a certain delay time (fixed),
signalled by the chiller led or heat pump led flashing. The flashing led indicates the operating modality used
when the unit will be restarted, respecting the protection time of the compressor.
CF34
Serial address
CF36
It allows to select the default displaying of the top and bottom:
•
0=
BEWIT
temperature is displayed in the top
•
1=
BEWOT
temperature is displayed in the top
•
2= no displaying in the top
•
3=
BAT1
temperature is displayed in the top
•
4= unit set point is displayed in the top (*)
•
5= unit status is displayed in the top (**)
•
6= Laser set is displayed in the top (NOT ENABLED FUNCTION)
•
7= no displaying in the top
•
8= the operating differential is displayed in the top
(*) the chiller set is displayed when the unit is in chiller modality, the heat pump set when the unit is in heat
pump modality or off with stand-by unit
(**) OnC is displayed when the unit is in chiller modality, OnH when the unit is in heat pump modality or off
with stand-by unit.
CF42
It allows to select the default displaying of the bottom:
•
0=
BEWIT
temperature is displayed in the bottom
•
1=
BEWOT
temperature is displayed in the bottom
•
2=
BCP1
temperature is displayed in the bottom
•
3=
BAT1
temperature is displayed in the bottom
•
4= unit set point is displayed in the bottom (*)
•
5= unit status is displayed in the bottom (**)
•
6= Laser set is displayed in the bottom
•
7= no displaying in the bottom
•
8= the operating differential is displayed in the bottom
(*) the chiller set is displayed when the unit is in chiller modality, the heat pump set when the unit is in heat
pump modality or off with stand-by unit
(**) OnC is displayed when the unit is in chiller modality, OnH when the unit is in heat pump modality or off
with stand-by unit.
CF43
It allows to select the default displaying of the top by remote control:
•
0=
BEWIT
temperature is displayed in the top
•
1=
BEWOT
temperature is displayed in the top
•
2= no displaying in the top
•
3=
BAT1
temperature is displayed in the top
•
4= unit set point is displayed in the top (*)
•
5= unit status is displayed in the top (**)
•
6= Laser set is displayed in the top (NOT ENABLED FUNCTION)
•
7= no displaying in the top
•
8= the operating differential is displayed in the top
(*) the chiller set is displayed when the unit is in chiller modality, the heat pump set when the unit is in heat
pump modality or off with stand-by unit
(**) OnC is displayed when the unit is in chiller modality, OnH when the unit is in heat pump modality or off
with stand-by unit.
Parameters
Description