OPERATING AND MAINTENANCE MANUAL
Electronic Board
MCCY - CY 013÷301
40
ENGLISH
EN
The data in this manual are not binding and they can be modified by the manufacturer without notice.
Reproduction of this manual is strictly prohibited.
A06
Low pressure /
temperature alarm
Analogue input
enabled if
BCP1
or
BAT1
< “set value”
“open collector” outlet / alarm relay
is activated
The buzzer is activated
The icon for general alarm flashes
The alarm code is displayed
Manual
Disabled if
BCP1
or
BAT1
> “set
value” and the resetting procedure
is carried out
A07
Antifreeze alarm
Analogue input
enabled if
BEWOT
< “set value”
“open collector” outlet / alarm relay
is activated
The buzzer is activated
The icon for general alarm flashes
The alarm code is displayed
Automatic
It becomes manual after “tripping
per hour”
Manual
Disabling: when the antifreeze
regulation probe
BEWOT
>
(
AR03
+
AR04
) in chiller modality;
and resetting procedure
NOTE
To lower the freeze protection setpoint, contact the MTA after-sales service and add a suitable amount of antifreeze
solutions to the system (see chap. 5.3 “Antifreeze protection” ).
A07
Antifreeze alarm
Digital input
enabled if
“open collector” outlet / alarm relay
is activated
The buzzer is activated
The icon for general alarm flashes
The alarm code is displayed
Automatic
It becomes manual after “tripping
per hour”
Manual
Disabling: digital input not enabled,
resetting procedure
A07
Antifreeze alarm
motocondensing
units
Digital input
enabled
“open collector” outlet / alarm relay
is activated
The buzzer is activated
The icon for general alarm flashes
The alarm code is displayed
Automatic
It becomes manual after “alarms
interventions”
Manual
Disabling: digital input disabled
and the resetting procedure is
carried out
A08
Flow meter alarm
(air/water or water/
water units)
Digital input
enabled
enabled for “time
set”
“open collector” outlet / alarm relay
is activated
The buzzer is activated
The icon for flow meter alarm
flashes
The alarm code is displayed
Automatic
It becomes manual after “tripping
per hour”
Manual
Disabling: Digital input disabled for
“time set” and reset procedure
A09
Compressor 1
thermal alarm
Digital input
enabled
“open collector” outlet / alarm relay
is activated
The buzzer is activated
The icon for general alarm flashes
The alarm code is displayed
Manual
Digital input disabled and the
resetting procedure is carried out
A10
Compressor 2
thermal alarm
Digital input
enabled
“open collector” outlet / alarm relay
are activated
The buzzer is activated
The icon for general alarm flashes
The alarm code is displayed
Manual
Digital input disabled and the
resetting procedure is carried out
A09-
A10
Compressor 1-2
thermal alarm
The alarm is
visualized but not
enabled during
“compressor thermal
delay time” after
compressor start up
Relay alarm + buzzer activated
If ID is not activated
Manual
To reset the alarm enter the
programming
A13
Compressor 1
maintenance alarm
Operating hours >
“set threshold”
“open collector” outlet / alarm relay
is activated
The buzzer is activated
The icon for general alarm flashes
The alarm code is displayed
Manual
Operating hours reset
A14
Compressor 2
maintenance alarm
Operating hours >
“set threshold”
“open collector” outlet / alarm relay
are activated
The buzzer is activated
The alarm code is displayed
Manual
Operating hours reset
A15
Water pump / outlet
fan (air/air)
maintenance alarm
Operating hours>
“set threshold”
“open collector” outlet / alarm relay
are activated
The buzzer is activated
The alarm code is displayed
Manual
Operating hour reset
COD.
MEANING
CAUSE
ACTION
RESET