OPERATING AND MAINTENANCE MANUAL
Trouble shooting
MCCY - CY 013÷301
59
ENGLISH
EN
The data in this manual are not binding and they can be modified by the manufacturer without notice.
Reproduction of this manual is strictly prohibited.
E
Low pressure switch or
alarm trips (LP)
Alarm displayed:
A02
E1
No refrigerant fluid in the
unit
(see also A5).
E1.1
• Refrigerant compressor
stops;
• the alarm A02 alternate with
the value of the
BEWIT
probe;
• main alarm relay tripped.
• the led of the
lights up;
Call a qualified refrigeration
technician to check for leaks
and replenish refrigerant
charge.
E2
The water upstream filter is
dirty, if installed
E2.1
See E1.1.
Clean or change the upstream
filter, if installed.
F
The compressor protection
device trips.
Alarm displayed:
A09 or A10
F1
Thermal load too high
combined with a situation
of refrigerant circuit
unloaded (also see A5).
F1.1
• The head and the body of the
compressor are very hot;
• the compressor stops and
tries to restart after a short
period (even a few seconds).
• The compressor protection
device trips
• Alarm displayed A09 or
A10
• The led of the icon
lights
up.
Call a qualified refrigeration
technician to check for leaks
and replenish refrigerant
charge.
F2
The scroll compressor
rotation direction is wrong
(only three-phases units).
F2.1
Refrigerant compressor
stops the unit does not
cool.
Invert two phases of the
electrical supply.
G
Digital display and all
LEDs off, main switch P1
off (I).
G1
The auxiliary board fuse
trip
G1.1
Measuring with a tester
the voltage at the
transformer secondary
winding connector, there
will be not tension
survey.
Check the causes of the fuse
tripping.
Replace the fuse.
G2
Abnormal power
consumption by one or
more control board
components.
G2.1
Despite presence of
power at the connectors
of the control board, the
display and all LEDs
remain unlit.
Try to turn the unit OFF and
ON again. If this doesn’t solve
the problem, contact the nearest
service centre.
H
Alarm displayed:
P1, P2, P3, P4
H1
BEWIT
,
BEWOT
,
BCP1
or
BAT1
probes damaged.
H1.1
• See problem;
• main alarm relay tripped.
Check that the temperature
probe is correctly connected to
the control board connectors
and that the cable is
undamaged. If necessary
replace the temperature sensor.
PROBLEM
CAUSE
SYMPTOM
REMEDY
Summary of Contents for MCCY-CY013 301