Appendix
The data in this manual are not binding and may be changed by the manufacturer without notice.
Reproduction of this manual, even partial, is strictly prohibited.
F
IRST
START
CHECKLIST
(
ONLY
CY
UNITS
)
Start
No
Yes
No
Yes
No
No
Yes
Persons not involved in the operations must be
kept clear of the area
Any alarms shown on unit display?
Water differential pressure switch working
correctly?
Connect high and low pressure gauges to check the
measured operating pressure values are correct
Setting high pressure value to approx. 14 bar gas
leaks > 3 grams/year are detected?
Start procedure terminated
Trip test:
Adjust the unit water gate
valves to reduce the flow rate
to the evaporator
Stop the unit and find the cause of the
problem
Check and/or renew the component
Stop the unit and find the cause
of the problem
Stop unit and find the cause of the leak
in compliance with EN 378-2
Yes
Summary of Contents for MCCY-CY013 301
Page 68: ......