535-PROF User's Manual
Chapter 5
33
Controller Set Up
Access Set Up
Return to Operation
Next menu
Next parameter
Next value
Access Tuning
Return to Operation
+
FAST
MENU
DISPLAY
+
FAST
MENU
MENU
▲
▼
MENU
DISPLAY
12. CONTACT 1
Defines the operation of the first digital input.
•
RECIPE. 1–7
Chooses the recipe number (uses Binary contact
1-3)
•
SETPT. 1–8
Chooses Local setpoint 1–8 (uses BCD contacts
1–4)
•
REM. SETPT.
Makes the remote setpoint active
D
MANUAL
Trips the controller to manual control
•
2ND. SETPT.
Makes the second setpoint active
•
2ND. PID
Makes the second set of PID values active
•
ALARM ACK.
Acknowledges alarms
•
RST. INHBT.
Deactivates the reset term
•
D.A./R.A.
Switches the control action
•
STOP A/T
Suspends the adaptive tune function
•
LOCK. MAN.
Locks controller in manual control
•
UP KEY
Remote function
•
DOWN KEY
Remote function
•
MENU KEY
Remote
MENU
key function
•
FAST KEY
Remote
FAST
key function
•
DISP KEY
Toggle between SP DEV or OUT%
•
COMM. ONLY
Status readable only through communications
•
START REC.
Runs the most recently selected recipe (de-
fault is RECIPE 1). Aborts recipe when deacti-
vated.
•
HOLD REC.
Holds running recipe at current position. Re-
sumes running of recipe when deactivated.
•
RESET REC.
Resets a running or held recipe to the begin-
ning. For linked recipes, resets to the beginning
of the first linked recipe. No action when deac-
tivated.
•
ABORT REC.
Aborts running or held recipe. No action when
deactivated.
•
NEXT SEG.
Advances running or held recipe to the end of
the current ramp or soak segment. No action
when deactivated
•
PV2.SWITCH
Switches between PV1 and PV2
CONTACT 1
MANUAL