Calibration
A-6
Appendix 4
535-PROF User's Manual
ANALOG IN
CALIBRATE
ANLG. OUT
CALIBRATE
CAL. 120mV, etc.
OUTPUT X, etc
5.0000
CAL. VREF
4 mA
OUTPUT "X"
DISPLAY ONLY
TO RESET
PUSH MENU
COMPLETED
RESET
RESET
SKIPPED
SCAN
HARDWARE
PRESS ACK
PRESS ACK
PRESS ACK
PRESS ACK
PRESS ACK
PRESS ACK
After two
seconds
PRESS
MENU
before two
seconds
MENU DATA
RESET
PRESS ACK
TEST
SLIDEWIRE
____%
SLIDEWIRE
PRESS MENU
PRESS MENU
PRESS MENU
mA CALIB.
COMPLETED
mA CALIB.
FAILED
PRESS ACK
PRESS ACK
PRESS MENU
PRESS MENU
PRESS MENU
COLD JUNC.
CALIBRATE
PRESS ACK
PV= –150 C
PRESS ACK
PRESS MENU
PRESS MENU
PRESS MENU
PRESS MENU
PRESS MENU
PRESS MENU
ANA. mA IN
CALIBRATE
JUMPER=mA
SET BOTH
PRESS ACK
PV1=20mA
PRESS ACK
Power Down
Move Jumpers
Power Up
PRESS ACK
PV2=20mA
Attach 20mA
to PV1
Press ACK
Attach 20mA
to PV2
Press ACK
If mA calibration values are
OK.
If mA calibration values are
out of range.
APPENDIX 4
CALIBRATION
•
To maintain optimum performance, once a year calibrate the analog input, the
cold junction and milliamp output (when used). To achieve published accuracy
specifications, follow directions carefully and use calibrated instruments of like
quality to those suggested.
•
If the controller is moved into an alternate case, or the hardware configuration is
changed, and the thermocouple input is needed, recalibrate the cold junction
for maximum accuracy. Failure to do so may result in small junction tempera-
ture (0.6°C/1.1°F).
Access the parts of the calibration menu as shown in
Figure A4.2.
Figure A4.2
Flowchart Calibration Menus
Figure A4.1
535 Rear Terminals for Calibration
1
2
3
4
5
6
7
8
16
15
14
13
12
11
10
9
17
18
19
20
21
22
23
24
32
31
30
29
28
27
26
25
PV 1–
PV 1+
PV 2–
PV 2+
RTD 3rd