535-PROF User's Manual
Chapter 5
59
Controller Set Up
Access Set Up
Return to Operation
Next menu
Next parameter
Next value
Access Tuning
Return to Operation
+
FAST
MENU
DISPLAY
+
FAST
MENU
MENU
▲
▼
MENU
DISPLAY
2. NEXT LINK
Defines which (if any) recipe will run after the current recipe has ended. Also
can place the output in manual at a specified percentage.
D
NONE
R
1 to # of configured recipes
•
NO OUTPUT
3. IDLE SP
Selects the setpoint to be used when the recipe starts or after it has completed.
D
LAST SP
use the previous setpoint
•
REMOTE SP
use the remote setpoint (if option is installed
and enabled)
R
-9999 to 99999
(decimal point defined by
DECIMAL
param-
eter)
4. SOAK HYST.
Defines the absolute value of the maximum allowable deviation from setpoint
either when a soak segment starts (if GUAR.SOAK = START SEG.) or any-
time during a soak segment (if GUAR.SOAK = WHOLE SEG.). If the deviation
exceeds this value, guaranteed soak will occur.
D
OFF
R
1 to 99999
(decimal point defined by DECIMAL param-
eter)
5. RAMP RT:##
For RAMP UNIT = RATE, defines the rate of rise or fall of the setpoint during
ramp segment ##, while approaching soak setpoint ##.
If
TIME BASE
= HOURS:MIN
If
TIME BASE
= MIN:SEC
D
OFF
D
OFF
R
1 to 99999/MIN
R
1 to 99999/SEC
The decimal point is defined by the DECIMAL parameter.
6. RAMP TM:##
For RAMP UNIT = TIME, defines the time for ramp segment ## to reach soak
setpoint ##.
If
TIME BASE
= HOURS:MIN
If
TIME BASE
= MIN:SEC
D
OFF
D
OFF
R
00:01 to 99:59 HR:MN
R
00:01 to 99:59 MN:SC
7. RAMP EV:##
Defines which events will be activated during ramp segment ##.
D
NONE
•
EVENT 1
•
EVENT 2
•
EVENT 12
SOAK HYST.
OFF
RAMP RT:##
OFF
RAMP TM:##
OFF
RAMP EV:##
NONE
NOTE:
To end programming, set
RAMP RT:###
or
RAMP TIM:##
to
OFF.
NEXT LINK
OFF
IDLE SP
LAST SP