Controller Set Up
58
Chapter 5
535-PROF User's Manual
Access Set Up
Return to Operation
Next menu
Next parameter
Next value
Access Tuning
Return to Operation
+
FAST
MENU
DISPLAY
+
FAST
MENU
MENU
▲
▼
MENU
DISPLAY
4. SHED TIME
Defines the time interval between communications activity before the controller
determines that communications is lost (“sheds”).
R
1 to 512 seconds
D
OFF
5. SHED MODE
Defines the state of the controller if communications is lost (“sheds”).
D
LAST MODE
Remain in automatic or manual control (last mode before
losing communications)
•
MANUAL
Trip to manual control
•
AUTOMATIC
Trip to automatic control
6. SHED OUT.
Defines the output if the unit sheds and trips to manual control. Choose values
based on the process.
Standard Control
On/Off Control
Velocity Prop Control
•
–5 to 105%
•
ON
•
CW
D
LAST OUT
D
OFF
•
CCW
D
OUTS. OFF
7. SHED SP
This defines the setpoint status if communications is lost.
D
LAST SP
Continues to use setpoint that was active prior
to losing communications
•
DESIG. SP
Goes to a designated setpoint value if
communications is lost.
8. DESIG. SP
Defines the value of the designated setpoint if communications is lost.
R
Any value in the process variable range
D
Dependent on the process variable range
RECIPE #
(# = 1 to 20) For each recipe number (as determined by the
RECIPES
parameter
in the
REC. CONF.
menu), you will set values for the following parameters:
1. CYCLES
Defines the number of times the recipe will run before ending or going to the
next linked recipe.
•
CONTINUAL
R
1 to 99
D
1
SHED SP
LAST SP
DESIG. SP
(D)
SHED OUT.
(D)
RECIPE #
CYCLES
CONTINUAL
SHED TIME
OFF
SHED MODE
LAST MODE