82
Chapter 7
535-PROF User's Manual
Applications
The decimal point is defined by the
DECIMAL
parameter.
7. The next parameter is
RAMP TM:##
(## = 1 to 12). It defines the time for
the current ramp segment (##) to reach the current soak setpoint (##). This
parameter will only appear if
RAMP UNIT =
TIME. Choices are:
D
OFF
ends recipe programming
R
00:01 to 99:59 HR:MN if TIME BASE = HOURS:MIN
R
00:01 to 99:59 MN:SC if TIME BASE = MIN:SEC
IMPORTANT:
For each
RAMP
segment, you will scroll through and set
values for the next six parameters. However, choosing OFF for either
RAMP
RT.##
or
RAMP TM##
will conclude the programming.
8. The next parameter is
RAMP EV:##
(## = 1 to 12). It selects which events
will be activated during the current ramp segment. Choices are:
D
NONE
•
EVENT 1
event output 1 is selected
•
EVENT 2
event output 2 is selected
•
EVENT 12
event outputs 1 and 2 are selected
•
EVENT 3
event output 3 is selected
•
EVENT 13
event outputs 1 and 3 are selected
•
EVENT 23
event outputs 2 and 3 are selected
•
EVENT 123 event outputs 1, 2 and 3 are selected
9. The next parameter is
SOAK SP:##
(## = 1 to 12). It defines the setpoint
after the current ramp segment (##) has completed. Choices are:
•
-9999 to 99999
R Dependent upon process variable range
The decimal point defined by the
DECIMAL
parameter
10. The next parameter is
SOAK TM:##
(## = 1 to 12). It defines the length
of the current soak segment. Time units are defined by the
TIME BASE
parameter in the
REC. CONF.
menu. Choices are:
D
OFF
Selecting off eliminates the SOAK and makes possible 2 or more
ramps to different setpoints.
R
00:01 to 99:59 HR:MN if TIME BASE = HOURS:MIN
R
00:01 to 99:59 MN:SC if TIME BASE = MIN:SEC
11. The next parameter is
SOAK EV:##
(## =1 to 12). It defines which
events will be activated during this soak segment. This parameter will only
appear if
SOAK TM:##
is not OFF. Choices are:
D
NONE
•
EVENT 1
event output 1 is selected
•
EVENT 2
event output 2 is selected
•
EVENT 12
event outputs 1 and 2 are selected
•
EVENT 3
event output 3 is selected
•
EVENT 13
event outputs 1 and 3 are selected
•
EVENT 23
event outputs 2 and 3 are selected
•
EVENT 123 event outputs 1, 2 and 3 are selected
12. The last parameter is
PID SET:##
(## =1 to 12). It selects which PID
set to use during the current ramp and soak segments. This parameter only
appears if
NO. OF PID
= SEG SELECT (in the
TUNING
menu). Choices are:
D
LAST SET