www.miinet.com
Moore Industries-International, Inc.
- 63 -
User’s Manual
238-741-00K
May 2019
Programmable Smart HART Temperature Transmitter
THZ
3
/ TDZ
3
SECTION 4
Dual Input:
The
Dual Input
menu will allow you to view and set Scaling and and Custom Curve for
the following Device Variables:
Backup 1-2, Backup 2-1, Average, Differential 1-2,
Differential 2-1, Absolute Differential, Low Select,
and
High Select.
Refer to Figure 4.9
for clarification, menu is shown for Backup 1-2 but is the same for any of the given Device
variables.
Note:
The
Dual Input
menu is only visible if
Advance Settings
is Enabled.
Note:
After making all desired changes enter
SEND
to update the unit.
Default Config
Config Wizards
Input
Dual Input*
Analog Output
HART Sengs
Display
System Config
Advance Sengs
Backup 1-2
Backup 2-1
Average
Differenal 1-2
Differenal 2-1
Absolute Differenal
Low Select
High Select
Backup 1-2 Scl En
Backup 1-2 EGU
Backup 1-2 Input Min
Backup 1-2 Input Max
Backup 1-2 Scale Min
Backup 1-2 Scale Max
Disabled
Enabled
inH2O
inHg
H2O
…..
Enter Backup 1-2
Inp ut Max
Enter Backup 1-2
Scale Min
Enter Backup 1-2
Scale Min
Backup 1-2 CC En
Backup 1-2 EGU
Backup 1-2 CC ID
Disabled
Enabled
inH2O
inHg
H2O
…..
CC 1
CC 2
CC 3
CC 4
Backup 1-2
Backup 1-2 EGU
Scaling
Custom Curve
All menus follow same
format as Backup 1-2
Select your Device Variable
and follow same flow.
Enter Backup 1-2
Inp ut Min
Figure 4.9.
TDZ
3
or THZ
3
Dual input