www.miinet.com
Moore Industries-International, Inc.
- 41 -
User’s Manual
238-741-00K
May 2019
Programmable Smart HART Temperature Transmitter
THZ
3
/ TDZ
3
SECTION 3
When installed in Zone 2 locations:
The THZ3 Temperature Transmitter shall be mounted within a tool-secured enclosure which
meets the requirements of ANSI/ISA-60079-0, ANSI/ISA-60079-15 and ANSI/ISA 61010-1 or
CAN/CSA-C22.2 No. 60079-0, CAN/CSA-C22.2 No. 60079-15 and CAN/CSA-C22.2
No. 61010-1 and is capable of accepting the applicable wiring methods wiring methods per
the NEC or the Canadian Electrical Code. The enclosure shall, at a minimum, meet the
requirements of IP54.
The non-metallic parts incorporated in the THZ3 DIN mount housing may generate an
ignition-capable level of electrostatic charge. The equipment shall not be installed in a location
where the external conditions are conducive to the build-up of electrostatic charge on such
surfaces. Additionally, the equipment shall only be cleaned with a damp cloth.
The THZ3 shall be provided with supply transient protection external to the apparatus such that
the voltage at the supply terminals does not exceed 119Vac peak or 119Vdc.
European Union Installations (ATEX 2014/34/EU Directive)
II (1) G [Ex ia Ga] IIC
II 3 (1) G Ex nA [ia Ga] IIC T4 Gc
When installed in non-hazardous locations:
The THZ3 shall be mounted within a tool-secured enclosure capable of accepting the applicable wiring
methods specified in EN 60079-14. The enclosure shall, at a minimum, meet the requirements of IP20.
When installed as Category 3 equipment and/or in Zone 2 locations
:
The THZ3 shall be mounted within a tool-secured enclosure which meets the requirements of
EN 60079-0 and EN 60079-15 and is capable of accepting the applicable wiring methods specified in
EN 60079-14. The enclosure shall, at a minimum, meet the requirements of IP54.
The non-metallic parts incorporated in the THZ3 DIN mount housing may generate an
ignition-capable level of electrostatic charge. The THZ3 shall not be installed in a location where
the external conditions are conducive to the build-up of electrostatic charge on such surfaces.
Additionally, the equipment shall only be cleaned with a damp cloth.
The THZ3 shall be provided with supply transient protection external to the apparatus such that
the voltage at the supply terminals does not exceed 119Vac peak or 119Vdc.