- 57 -
User’s Manual
238-741-00K
May 2019
Programmable Smart HART Temperature Transmitter
THZ
3
/ TDZ
3
SECTION 4
Input Menu:
The Setup menu allows you to access the following menus:
Filter, PV Damping, Configure
Sensor, and Ranging & Mapping.
Filter [60Hz]
– This setting is used to configure the input filter. The filter is designed to
reduce the effects of mains induced noise. The input filter frequency value should be set to the
frequency of the local AC supply–either 50Hz or 60Hz.
PV Damping [DISABLED, 0 seconds]
– PV Damping allows you to introduce a delay
(0-60 seconds) into the response of your unit in order to stop short-lived spikes from initiating
faults and generating fault messages. The damping time setting is the time PV takes to make a
63% change in response to a step change.
Configure Sensor
–
The
Configure Sensor
menu
allows you to access to the following list for
configuration:
Configure Input Types, RJC Temp, Sensor 1, and Sensor 2
refer to Figure 4.5
.
Note:
After making all desired changes enter
SEND
to update the unit.
Figure 4.5.
TDZ
3
or THZ
3
Input menu
Filter
PV Damping
Configure
Sensor
Ranging and
Mapping
2W
3W
4W
Pt3850 100 ohm
Pt3850 200 ohm
Pt3850 400 ohm
Pt3850 500 ohm
Pt3850 1000 ohm
Pt3902 100 ohm
Pt3902 200 ohm
Pt3902 400 ohm
Pt3902 500 ohm
Pt3902 1000 ohm
Pt3916 100 ohm
Ni6720 120 ohm
Cu 427 9.035 ohm
Configure
Input Types
RJC Temp
Sensor 1
Sensor 2
Sensor 1 TYPE
1. Resistance
2. mV
3. Potenometer
4. RTD
5. T/C
50 Hz
60 Hz
Enter
Damping
Time Secs
4K
2K
1K
500
250
125
1K
500
250
125
62.5
31.25
Sensor 2 TYPE
1. Off
2. Same as Senor 1
3. Configure
Ind ependantly
4K
2K
1K
500
250
125
2W
3W
4W
degC
degF
degR
Kelvin
Disabled
Enabled
degC
degF
degR
Kelvin
degC
degF
degR
Kelvin
Type J
Type K
Type E
Type T
Type R
Type S
Type B
Type N
Type C
RJC Temp EGU
See Figure 4.6
See Figure 4.8