Programmable Multi-Axis Servo Drive Power Supply Unit Operation Manual
ID no.: CA97556-001 Date: 03/2015
moog
24
Mechanical installation
H
B
T
A
C
Ø G
PE
Figure 2.15 Dimensional drawing, mains filter, example for size 5 and size 6A
2.8
Mains filter installation
Arrange the components so as to ensure sufficient air circulation and cooling.
Mark out the position of the tapped holes on the backing plate.
Cut a tap for each fixing screw in the backing plate.
Take into account the bend radius of the connecting cables.
Dimensional drawings/hole spacing see Figure 2.15 and Table 2.5.
Mount the mains filter on the backing plate.
The tapping area will provide you with good, full-area contact. The contact area must be
metallically bright.
2.8.1
Dimensions
For size
Size 5
Size 6A
For model
G396-026
G396-050
G396-075
G396-110
Type
FFU 3 x 56 K
FFU 3 x 80 K
FFU 3 x 130 K
FFU 3 x 180 K
B (width)
85 (3.35)
80 (3.15)
90 (3.54)
130 (5.12)
H (height)
250 (9.84)
270 (10.63)
270 (10.63)
380 (14.96)
T (depth)
90 (3.54)
135 (5.31)
150 (5.91)
180 (7.09)
A
60 (2.36)
60 (2.36)
65 (2.56)
102 (4.02)
C
235 (9.25)
225 (8.86)
255 (10.04)
365 (14.37)
G Ø
5.4 (0.21)
6.5 (0.26)
6.5 (0.26)
6.5 (0.26)
Mounting screws
M5
M6
M6
M6
Weight
1.9 kg (4.19 lb)
2.6 kg (5.73 lb)
4.2 kg (9.26 lb) 6.0 kg (13.23 lb)
All dimensions in mm (in) and excluding terminals/connectors
Table 2.5 Mains filter dimensions
1.
2.