Electrical installation
3.6.2
Precharge and mains synchronisation (X21) for size 5 and
size 6A
The DC link is precharged via terminal X21/L1,L2,L3 (Figure 3.15, p. 38). At a defined
DC link voltage the contact of the internal relay on terminal X21/HREL is closed. The
mains contactor closes and switches the supply system to terminal X12/ L1,L2,L3. The
Power Supply Unit is synchronised with the mains via terminal X21/L1,L2,L3. Technical
data of mains contactor see section A.11, p. 73.
ATTENTION!
The cable must be protected by a circuit-breaker. Ensure the correct phase
angle of the conductors during installation (Figure 3.15, p. 38). Technical
data of circuit-breaker see A.12, p. 73.
Specification of precharge and mains synchronisation X21
Precharge and
mains synchro-
nisation
(L1, L2, L3)
X21
HREL
L3
N
L1
L2
•
U = 400/460/480 V AC
•
I
Precharge
= 20 A (falling over a period of < 1.5 s)
•
I
Synchronisation
< 100 mA
•
Cable cross-section = 1.0 ... 1.5 mm
2
(0.002 ... 0.0023 in
2
)
•
(N: Not used)
Auxiliary relay
(HREL)
•
Max values of connection
•
U
Max
= 30 V DC / I
Max
= 6 A
Table 3.4 Specification of precharge and mains synchronisation X21
!
NOTE:
Do not use the plug as a "switch" for a reset.
Specification of control supply
Control
supply
X9
1/+
2/−
•
U
V
= 24 V DC -20 % +10 %, stabilised and smoothed.
•
Max. Start-up/continuous current see Table A.7, p. 69
•
Back-up fuse rating for terminal maximum 10 A
•
Internal polarity reversal protection
•
The power supply unit used must have a safe and reliable isolation against
the mains system according to EN 50178 or IEC/EN 61800-5-1.
•
Internally wired with X10
X10
1/+
2/−
•
Internally wired with X9
Table 3.3 Specification of control supply