Commissioning
4.2.9
Programming monitoring of the braking resistor
8.
Braking resistor setting.
y
Set the braking resistor:
− P-0741
Resistance
− P-0742
Rated power
− P-0743
Maximum energy
− P-0745
Threshold value for warning
y
Set parameter
P-0740
to 1 in order to activate the braking resistor.
Figure 4.6 Parameter editor - parameter
P-0740
NOTE:
For the parameters to take effect even after a restart, the changed settings
must be permanently saved to the device and a 24 V reset performed.
This completes all necessary parameter settings.
4.2.8
Setting DC link voltage
7.
The Power Supply Unit regulates the DC link voltage to an internally preset fixed value. At an
input voltage of 400 V
AC
the DC link voltages 650 and 770 V
DC
are possible. At an input voltage
of 460 and 480 V
AC
the DC link voltage 770 V
DC
is possible.
y
Set the DC link voltage to 650 or 770 V
DC
P-0410
.
Figure 4.5 Parameter editor - parameter
P-0410