2.1.6 MAINTENANCE DATA
(1) Trouble shooting
(a)
Trouble shooting to be performed prior to exchanging PCB, (Printed circuit board) [Common to all models]
All the models described in this chapter are controlled by a microcomputer. When providing maintenance service to customers it
is necessary to understand the function controlled by a micro computer thoroughly, so as not to mistakenly identify correct opera-
tions as mis-operations. It is also necessary to perform the following simple checks before conducting detailed checks or exchang-
ing printed circuit board.
Before exchanging Printed circuit board
Claim call from the user
Ascertain the nature of the claim.
Ascertain the operation status.
Does the trouble occur again?
Is this nonsense claim?
Operate the unit.
Does the trouble occur again?
Temporarily turn off the power source and
turn it on again in about 1 min. and turn the
unit on again.
YES
No
YES
YES
Does the trouble occur again?
Disconnect connectors and connect them
again.
Operate the unit again after confirming that the fuse
and the varistor equipped on PCB does not burn out.
Carry out checks according to detailed
check process (See later page)
Unit did not cool, etc.
¡
Is the power on?
¡
Is the thermostat setting correct?
(Not too high?)
¡
Is the unit in a timer operation?
¡
Does user understand function?
etc.
¡
Explain the function of the unit to user.
No need for PCB change
Check further the status when the trouble occured
(such as the timer of occurence, power failures, thun-
der, use status of other electrical appliances, etc).
Clarify the reason for the problem and explain it thor-
oughly to the user.
No need for PCB change
Microcomputer runaway due to power source
conditions is a possible cause.
No need for PCB change
The cause is defective connector contact.
YES
No
No
No
Summary of Contents for SRK10CES
Page 2: ...TECHNICAL MANUAL...
Page 204: ...202 MEMO...
Page 213: ...211...
Page 227: ...225...
Page 233: ...231...
Page 236: ...CRBE0226 1 3 4 2 5 6 7 8 9 10 11 12 13 PANEL FAN ASSY 234...
Page 244: ...CRBE0228 9 15 7 8 1 2 4 5 6 12 13 14 10 11 3 PANEL FAN ASSY 242...
Page 248: ...CRBE0227 11 15 16 1 2 3 5 6 7 8 9 12 13 14 4 10 PANEL FAN ASSY 246...
Page 252: ...CRBE0221 12 16 17 1 2 3 5 6 7 8 9 10 13 16 14 15 4 11 PANEL FAN ASSY 250...
Page 256: ...05 0 CRBE0224 2 1 5 16 3 9 11 12 4 7 8 6 6 17 17 10 13 15 14 PANEL FAN ASSY 254...
Page 260: ...2005 ROOM AIR CONDITIONING TECHNICAL HANDBOOK...