80
-
(iv) Fan operation
2
(v)
Standby operation
1) Operation content
1) Operation content
Inverter command speed (rps)
0
Indoor fan motor
OFF
Outdoor fan motor
2nd Speed
Flap and louver
Fully closed/ Center
(15) ECONOMY operation
(ECONO button on remote control: ON)
(a)
The set temperature is raised by 1.5ºC (0.5ºC every one hour) at cooling operation and lowered by 2.5ºC (Steps of 1ºC, 1ºC and
0.5ºC every one hour) at heating operation to continue the operation with the following contents.
(b)
Detail of operation
CnT Input
A Unit
B Unit
OFF
OFF
*ON
ON
ON
ON
OFF
OFF
OFF
ON
ON
ON
OFF
OFF
OFF
Note (1) The ON with the * mark indicates an
ON operation using the remote control
unit switch, etc.
(ii)
When Jumper wire J1 on the PCB of indoor unit is cut at the field or “PULSE INPUT” is selected in the wired remote
control’s indoor unit settings.
Input signal to CnT becomes valid at OFF
→
ON only and the motion of air conditioner [ON/OFF] is inverted.
CnT Input
A Unit
B Unit
OFF
OFF
ON
ON
OFF
ON
OFF
ON
ON
OFF
OFF
*ON
(16) External control (remote display)/control of input signal
Make sure to connect the standard remote control unit. Control of input signal is not available without the standard remote control unit.
(a)
External control (remote display) output
Following output connectors (CNT) are provided on the printed circuit board of indoor unit.
(i)
Operation output:
Power to engage DC 12V relay (provided by the customer) is outputted during operation.
(ii)
Heating output:
Power to engage DC 12V relay (provided by the customer) is outputted during the heating operation.
(iii) Compressor ON output:
Power to engage DC 12V relay (provided by the customer) is outputted while the compressor is
operating.
(iv) Error output:
When any error occurs, the power to engage DC 12V relay (provided by the customer) is outputted.
(b) Control of input signal
Control of input signal (switch input, timer input) connectors (CNT) are provided on the control circuit board of the indoor unit.
However, when the operation of air conditioner is under the Center Mode, the remote control by CnT is invalid.
(i)
If the factory settings (Jumper wire J1 EXTERNAL INPUT on the PCB) are set, or “LEVEL INPUT” is selected in the wired
remote control’s indoor unit settings.
1) Input signal to CnT OFF
→
ON Air conditioner ON
2) Input signal to CnT ON
→
OFF Air conditioner OFF
Model
SRK22ZEV-S
Item
Operation mode
Cooling
Heating
Inverter command speed
12~46 rps
12~60 rps
Indoor fan motor
2nd, 4th speed
3rd, 5th speed
Outdoor fan motor
3rd~5th speed
Inverter command speed (rps)
0
Indoor fan motor
OFF
Outdoor fan motor
Determined by stop mode
Flap and louver
Fully closed/ Center
Summary of Contents for SRK10CES
Page 2: ...TECHNICAL MANUAL...
Page 204: ...202 MEMO...
Page 213: ...211...
Page 227: ...225...
Page 233: ...231...
Page 236: ...CRBE0226 1 3 4 2 5 6 7 8 9 10 11 12 13 PANEL FAN ASSY 234...
Page 244: ...CRBE0228 9 15 7 8 1 2 4 5 6 12 13 14 10 11 3 PANEL FAN ASSY 242...
Page 248: ...CRBE0227 11 15 16 1 2 3 5 6 7 8 9 12 13 14 4 10 PANEL FAN ASSY 246...
Page 252: ...CRBE0221 12 16 17 1 2 3 5 6 7 8 9 10 13 16 14 15 4 11 PANEL FAN ASSY 250...
Page 256: ...05 0 CRBE0224 2 1 5 16 3 9 11 12 4 7 8 6 6 17 17 10 13 15 14 PANEL FAN ASSY 254...
Page 260: ...2005 ROOM AIR CONDITIONING TECHNICAL HANDBOOK...