2 SPECIFICATIONS
2.1 Performance Specifications
19
2
*1 Except for the conditions under noise influence
For the noise immunity, withstand voltage, insulation resistance, and others in a programmable controller system which uses
a temperature control module, refer to the following.
MELSEC iQ-R Module Configuration Manual
How to calculate the accuracy
Calculate the accuracy in the following method.
Accuracy (
) = full scale
indication ac cold junction temperature compensation accuracy
Ex.
Accuracy at the input range set to "38: Thermocouple K Measured Temperature Range (-200.0 to 400.0
)", operating
ambient temperature of 35
, and the temperature process value (PV) of 300
(full scale)
(indication accuracy) + (cold junction temperature compensation accuracy)
= (400.0
- (-200.0
))
(
0.007) + (
1.0
)
=
5.2
Withstand voltage
Between input terminals and programmable controller power supply: 500VAC, 1 minute
Between input channels: 500VAC, 1 minute
Insulation resistance
Between input terminals and programmable controller power supply: 500VDC, 20M
or
higher
Between input channels: 500VDC, 20M
or higher
Heater
disconnection
detection
specifications
Current sensor
Refer to the following.
Page 27 Current sensor for heater
Input accuracy
Full scale
(
1.0%)
Number of alert delay
3 to 255 times
Number of occupied I/O points
16 points, 1 slot (I/O assignment:
intelligent 16 points)
32 points, 2 slots (I/O assignment: empty 16
intelligent 16 points)
External connection system
18-point terminal block
18-point terminal block
2
Applicable wire size
0.3 to 0.75mm
2
(22 to 18 AWG)
Applicable solderless terminal
R1.25-3 (The solderless terminal with an insulation sleeve cannot be used.)
Internal current consumption
0.28A
0.31A
Weight
0.22kg
0.34kg
External
dimensions
Height
106mm (Base unit mounting part:
98mm)
106mm (Base unit mounting part: 98mm)
Width
27.8mm
56mm
Depth
110mm
110mm
Item
R60TCTRT2TT2
R60TCRT4
R60TCTRT2TT2BW
R60TCRT4BW
Summary of Contents for MELSEC iQ-R series
Page 2: ......
Page 13: ...11 MEMO ...
Page 15: ...13 CONTENTS TRADEMARKS 82 ...
Page 19: ...1 PART NAMES 17 1 MEMO ...
Page 28: ...26 4 PROCEDURES BEFORE OPERATION MEMO ...
Page 52: ...50 6 INSTALLATION AND WIRING 6 5 Unused Channel Setting MEMO ...
Page 79: ...APPENDIX Appendix 1 External Dimensions 77 A MEMO ...
Page 81: ...I 79 MEMO ...
Page 85: ......