FX0N-32NT-DP Profibus-DP Interface Unit
Wiring and Mounting 2
2-4
2.2
Wiring
2.2.1
EC and EMC Conformity
Using FX
0N
For compliance to EC and EMC regulations it is necessary to fit a ferrite noise filter to the
AC power lines of the FX
0N
main unit or extension unit from which the 32NT-DP 24V power
should be taken. (see Figure 2.3.) The filter should be similar to Würth Electonik’s part
number 742 710 0 B (impedance:4MHz, 80
Ω
; 25MHz, 139
Ω
; 100MHz, 207
Ω
) and fitted as
close to the unit as possible.
It is also necessary to install both the FX
0N
main unit, extension unit/block and the
32NT-DP slave unit in a metal cabinet.
Using FX
1N
, FX
2N
and FX
2NC
Series PLC
For compliance to EC and EMC regulations it is also necessary to install both the FX
1N
,
FX
2N
or FX
2NC
main unit, extension unit/block and the 32NT-DP slave unit in a metal
cabinet.