FX0N-32NT-DP Profibus-DP Interface Unit
Setting Operation 5
5-2
5.1.2
Setting the Number and Format of Input and Output Words in the DP-master
The 32NT-DP supports only word data format and word consistency. Combinations of 2
modules and 4 modules can be configured.
The configurations shown in the following table are possible.
Table 5.1: Setting the Number and Format of Input and Output Words
Module
Configuration
1
2
3
4
5
1
st
16 words input
16 words input
4 words input
16 words input
4 words input
2
nd
16 words output 16 words output 4 words output
4 words output 16 words output
3
rd
4 words input
-
-
-
-
4
th
4 words output
-
-
-
-