Power Supply Wiring
1) When connecting a 32NT-DP to an AC power supply type PLC of the FX
0N
, FX
1N
or FX
2N
Series, the 24V required by the 32NT-DP needs to be supplied from the FX
0N
, FX
1N
or FX
2N
Series PLC. For power supply wiring of the PLC, refer to each series Hardware Manual.
Figure 2.3: FX
0N
, FX
1N
and FX
2N
Series AC Power Supply Type PLC
*1 It is necessary to fit a ferrite noise filter to the AC power lines of the FX
0N
main unit or
extension unit from which the 32NT-DP 24V power should be taken. The filter should be
similar to Würth Electonik’s part number 742 710 0 B (impedance:4MHz, 80
Ω
; 25MHz,
139
Ω
; 100MHz, 207
Ω
) and fitted as close to the unit as possible.
24V
0V
FX
0N
, FX
1N
, FX
2N
Series
AC power supply type PLC
FX
0N
-32NT-DP
24V+ 24VG
L N
Grounding resistance of 100
Ω
or less (Class D)
100 - 240V AC
*1