FX0N-32NT-DP Profibus-DP Interface Unit
Wiring and Mounting 2
2-7
2.2.3
Profibus-DP Wiring
To connect the 32NT-DP to a Profibus-DP network use only the Profibus connectors and
shielded twisted-pair cable complying with EN50170. For Profibus connectors see the Profibus
connector manual.
Figure 2.5: Wiring
For Profibus connector,
refer to Figure 2.6.
Shielded twisted-pair
cable complying with
EN50170 to Profibus-DP
network
Grounding plate
Grounding
resistance of
100
Ω
or less
(Class D)
For noise prevention please attach at least 50mm
(1.97") of the twisted-pair cable along the
grounding plate to which the ground terminal is
connected.
24+ 24G
FG
DC power supply type PLC: Supply from the external power supply.
AC power supply type PLC: Supply from the service power supply of PLC.
Further information, refer to subsection 2.2.2.
FX
0N
-32NT-DP
Profibus-DP Interface Unit