100
PHOTOS & ILLUSTRATION
DISASSEMBLY PROCEDURE
O-ring
Plastic
bag
Female
Male
O-ring
Photo 23-1
Photo 23-2
Photo 23-3
Photo 23-4
Photo 23-5
Photo 23-6
Photo 23-7
Photo 23-8
23. How to detach and attach the quick connection
Refer to the following steps when detaching and attaching the
quick connection.
(1) Remove the clip. (Photos 23-1 and 23-2)
(2) Separate the connected parts to remove the O-ring. (Photo
23-3)
• Do not reuse the removed O-ring.
• Wipe off if dirt or foreign matters are found on the sealing
surface where the O-ring touches.
(3)
Apply grease on the O-ring using a plastic bag, etc. (Photo
23-4)
(4) Attach the O-ring to the male part of quick connection. (Pho
-
to 23-5)
• Keep the O-ring free from dirt or foreign matters.
(5) Connect the male and female parts of the quick connection.
(Photo 23-6)
(6) Attach the clip. (Photo 23-7)
• Ensure to attach the wider diameter of the clip to the fe
-
male side. Failure to do so it may cause water leak at the
connected part. (Photo 23-8) (For the same diameter
quick connection, following this note is not necessary.)
Clip
Clip
Gap
Clip
OCH570C