9 TROUBLESHOOTING
9.3 When the QD62(E/D) Does Not Normally Count
Check item
Action
Check the external wiring and correct the error.
Is the external wiring of
φ
A and
φ
B normal?
The module may miscount when ABCOM terminal is connected to
a pulse signal.
Connect the ABCOM terminal with external power (5V/12V/24V) or
GND terminal (refer to Section 4.4.2).
Is the maximum speed of input pulse within the range
of the counting speed made on the intelligent function
module switch setting?
Correct the counting speed setting in the intelligent function
module switch setting to meet the maximum speed of the input
pulse.
Does the input pulse waveform meet the performance
specifications?
Check the pulse waveform with synchronoscope. When the input
pulse does not meet the performance specifications, input the
pulse which meets the performance specifications.
Are the count value data treated in 32-bit binary in the
sequence program?
Correct the sequence program so that the count value data can be
treated in 32-bit binary.
Are the shielded twisted pair cables used for pulse
input wiring?
Use the shielded twisted pair cables for pulse input wiring.
Doesn't any noise come from the ground part of the
QD62(E/D)?
Separate the ground cable of the QD62(E/D) from the ground part.
When the QD62(E/D) case touches to the ground part, separate it.
Has the measures against noise been taken to the
adjacent devices and inside the control panel?
Take noise reduction measures (e.g. attach a CR surge
suppressor to the magnet switch).
Is the distance between the high voltage equipment
and pulse input line kept enough?
Bundle the pulse input lines and put them in a single tube, and
keep a distance of 150 mm (5.91 inch) or more with the power line
even inside the control panel.
Has the same count been input for both CH1 and
CH2 and are the count values the same?
When the count values are different, this is a hardware error.
Contact our branch office or distributor for consultation and give
details of the problem.
Summary of Contents for QD62
Page 1: ......
Page 2: ......
Page 13: ...A 11 A 11 MEMO ...
Page 55: ...4 18 4 18 MELSEC Q 4 SETUP AND PROCEDURE BEFORE STARTING THE OPERATION MEMO ...
Page 97: ...8 5 8 5 MELSEC Q 8 PROGRAMMING 3 Program example a Set only when the linear counter is used ...
Page 100: ...8 8 8 8 MELSEC Q 8 PROGRAMMING 2 Program example a Set only when the ring counter is used ...
Page 127: ......
Page 128: ......