3 - 1 3 - 1
MELSEC-Q
3 SPECIFICATIONS
3 SPECIFICATIONS
The following describes the performance specifications, I/O signals for the
programmable controller CPU and buffer memory specifications of the QD62(E/D).
For the general specifications of the QD62(E/D), see the User's Manual for the CPU
module used.
3.1 Performance Specifications
The following describes the performance specifications of the QD62(E/D):
(1) QD62 (DC input sinking output type) performance specifications
Model name
Item
QD62
Counting speed switch settings 1
200 k (100 k to 200 kPPS)
100 k (10 k to 100 kPPS)
10 k (10 kPPS or less)
I/O occupied points
16 points (I/O assignment: Intelligent 16 points)
Number of channels
2 channels
Phase
1-phase input, 2-phase input
Count input
signal
Signal level (
φ
A,
φ
B)
5/12/24 V DC 2 to 5 mA
Counting speed (max) 2
200 kPPS
100 kPPS
10 kPPS
Counting range
32-bit signed binary values (–2147483648 to 2147483647)
Model
UP/DOWN Preset c Ring counter function
Counter
Minimum count pulse
width (Duty ratio 50 %)
2.5 2.5
5
(Unit: s)
(Min. phase differential for
2-phase input: 1.25
μ
s)
5
5
10
(Unit: s)
(Min. phase differential for
2-phase input: 2.5
μ
s)
50 50
100
(Unit: s)
(Min. phase differential for
2-phase input: 25
μ
s)
Comparison range
32-bit signed binary values
Coincidence
output
Comparison result
Set value < Count value
Set value = Count value
Set value > Count value
Preset
External
input
Function start
5/12/24 V DC
2 to 5 mA
External
output
Coincidence output
Transistor (sinking type) output: 2 points/channel
12/24 V DC 0.5 A/point 2 A/common
5V DC internal current consumption
0.30 A
Weight
0.11 kg
1: The counting speed switch settings can be set using the intelligent function module switch.
2: Counting speed is affected by pulse rise and fall time. Possible counting speeds are shown in the following
table. Note that if a pulse that has a large rise and/or fall time is counted, a miscount may occur.
Counting speed switch settings
200 k
100 k
10 k
Rise/fall time
Both 1 and 2 phase input
t = 1.25
μ
s or less
200 kPPS
100 kPPS
10 kPPS
t = 2.5
μ
s or less
100 kPPS
100 kPPS
10 kPPS
t = 25
μ
s or less
—
10 kPPS
10 kPPS
t = 500
μ
s
— —
500 PPS
t
t
3
Summary of Contents for QD62
Page 1: ......
Page 2: ......
Page 13: ...A 11 A 11 MEMO ...
Page 55: ...4 18 4 18 MELSEC Q 4 SETUP AND PROCEDURE BEFORE STARTING THE OPERATION MEMO ...
Page 97: ...8 5 8 5 MELSEC Q 8 PROGRAMMING 3 Program example a Set only when the linear counter is used ...
Page 100: ...8 8 8 8 MELSEC Q 8 PROGRAMMING 2 Program example a Set only when the ring counter is used ...
Page 127: ......
Page 128: ......