7 - 18 7 - 18
MELSEC-Q
7 UTILITY PACKAGE (GX Configurator-CT)
[Explanation of items]
(1) Items
Setting item : Displays I/O signals and buffer memory names.
Current value : Monitors the I/O signal states and present buffer memory values.
Setting value : Enter or select values to be written into the buffer memory for test
operation.
(2) Command buttons
Current value display
Displays the current value of the item selected.
(This is used to check the text that cannot be
displayed in the current value field. However, in
this utility package, all items can be displayed in
the display fields).
Make text file
Creates a file containing the screen data in text
file format.
Start monitor / Stop monitor Selects whether or not to monitor current values.
Execute test
Performs a test on the selected items. To select
more than one item, select them while holding
down the Ctrl key.
Close
Closes the screen that is currently open and
returns to the previous screen.
REMARK
The following explains an example to change settings for the selected test operation
to the following:
• Counter function selection setting
: Sampling counter function
• Counter function selection start command (Y06) : ON
• Sampling/periodic setting [unit: 10 ms]
: 1000 ms
(1) Set "Sampling counter function" in the setting value field for CH Counter
function selection setting.
(2) Set "ON" in the setting value field for CH Counter function selection start
command (Y06).
(3) Click the setting value field for CH Sampling/periodic setting [unit: 10 ms].
(4) After entering the sampling time, press the Enter key.
At this point, nothing has been written to the QD62 (E/D).
(5) Select the setting value fields that were specified in steps 1 to 4 while holding
down the Ctrl key.
Multiple items can also be selected by dragging with the mouse.
(6) Click Execute test to execute write operation.
Once write operation is completed, the values that were written will be displayed
in the current value field.
Summary of Contents for QD62
Page 1: ......
Page 2: ......
Page 13: ...A 11 A 11 MEMO ...
Page 55: ...4 18 4 18 MELSEC Q 4 SETUP AND PROCEDURE BEFORE STARTING THE OPERATION MEMO ...
Page 97: ...8 5 8 5 MELSEC Q 8 PROGRAMMING 3 Program example a Set only when the linear counter is used ...
Page 100: ...8 8 8 8 MELSEC Q 8 PROGRAMMING 2 Program example a Set only when the ring counter is used ...
Page 127: ......
Page 128: ......