3 - 11 3 - 11
MELSEC-Q
3 SPECIFICATIONS
3.5 Interface with External Devices
The table below lists the external device interface for the QD62(E/D).
(1) QD62 (DC input sinking output type)
Terminal
number
1
I/O
classification
Internal circuit
CH1
CH2
Signal name
Operation
Input voltage
(guaranteed value)
Operating current
(guaranteed value)
When ON
21.6 to 26.4 V
2 to 5 mA
A20
A13 Phase A pulse input 24 V
When OFF
5 V or less
0.1 mA or less
When ON
10.8 to 13.2 V
2 to 5 mA
B20
B13 Phase A pulse input 12 V
When OFF
4 V or less
0.1 mA or less
When ON
4.5 to 5.5 V
2 to 5 mA
A19
A12 Phase A pulse input 5 V
When OFF
2 V or less
0.1 mA or less
B19 B12
ABCOM
—
When ON
21.6 to 26.4 V
2 to 5 mA
A18
A11 Phase B pulse input 24 V
When OFF
5 V or less
0.1 mA or less
When ON
10.8 to 13.2 V
2 to 5 mA
B18
B11 Phase B pulse input 12 V
When OFF
4 V or less
0.1 mA or less
When ON
4.5 to 5.5 V
2 to 5 mA
A17
A10 Phase B pulse input 5 V
When OFF
2 V or less
0.1 mA or less
1/3W
1/10W
1/16W
1/3W
1/10W
1/16W
4.7k
3.3k
470
4.7k
3.3k
470
— —
—
—
When ON
21.6 to 26.4 V
2 to 5 mA
B17
B10 Preset input 24 V
When OFF
5 V or less
0.1 mA or less
When ON
10.8 to 13.2 V
2 to 5 mA
A16
A09 Preset input 12 V
When OFF
4 V or less
0.1 mA or less
When ON
4.5 to 5.5 V
2 to 5 mA
B16
B09 Preset input 5 V
When OFF
2 V or less
0.1 mA or less
A15 B08
CTRLCOM
Response
time
OFF
ON
0.5 ms or less
ON
OFF
1 ms or less
When ON
21.6 to 26.4 V
2 to 5 mA
B15
B08 Function start input 24 V
When OFF
5 V or less
0.1 mA or less
When ON
10.8 to 13.2 V
2 to 5 mA
A14
A07 Function start input 12 V
When OFF
4 V or less
0.1 mA or less
When ON
4.5 to 5.5 V
2 to 5 mA
B14
B07 Function start input 5 V
When OFF
2 V or less
0.1 mA or less
Input
1/3W
1/10W
1/10W
1/3W
1/10W
1/10W
10k
5.6k
2k
1/10W
1k
10k
5.6k
2k
1/10W
1k
— —
—
Response
time
OFF
ON
0.5 ms or less
ON
OFF
1 ms or less
A06 A05
EQU1
(Coincidence output point No. 1)
B06 B05
EQU2
(Coincidence output point No. 2)
Operating voltage 10.2 to 30 V
Maximum load current 0.5 A/point, 2 A/common
Maximum voltage drop when ON 1.5 V
Response time OFF
ON 0.1 ms or less
ON
OFF 0.1 ms or less (rated load,
resistive load)
B02, B01
12/24 V
Output
FUSE
To the fuse
broken detection
circuit
A02, A01
0 V
Input voltage 10.2 to 30 V
Current consumption 8 mA (TYP 24 V DC)
1: Terminal numbers A03, A04, B03 and B04 are not used.
Summary of Contents for QD62
Page 1: ......
Page 2: ......
Page 13: ...A 11 A 11 MEMO ...
Page 55: ...4 18 4 18 MELSEC Q 4 SETUP AND PROCEDURE BEFORE STARTING THE OPERATION MEMO ...
Page 97: ...8 5 8 5 MELSEC Q 8 PROGRAMMING 3 Program example a Set only when the linear counter is used ...
Page 100: ...8 8 8 8 MELSEC Q 8 PROGRAMMING 2 Program example a Set only when the ring counter is used ...
Page 127: ......
Page 128: ......