8 - 2 8 - 2
MELSEC-Q
8 PROGRAMMING
8.1.1 Program example when GX Configurator-CT is used
(1) List of devices
Device Function
D0 to D1
Device that current value is written by auto refresh
D2 to D3
Device that latch count value is written by auto refresh
D4 to D5
Device that sampling count value is written by auto refresh
D6 to D7
Device that periodic pulse count previous value is written by auto refresh
D8 to D9
Device that periodic pulse count present value is written by auto refresh
D10
Overflow status storage
D20 to D35
Interrupt enabled flag storage for the IMASK instruction
X10
Count operation start signal
X11
Current value read signal
X12
Coincidence output data setting signal
X13
Preset command signal
X14
Count operation stop signal
X15
Coincidence LED clear signal
X16
Counter function execution start signal
X17
Counter function execution stop signal
X18
Latch count data read signal
X19
Latch execution signal
X1A
Sampling count data read signal
X1B
Sampling count start signal
X1C
Periodic pulse count data read signal
X1D
Periodic pulse count start signal
QX10 (X10 to X1F)
Y20
Coincidence confirmation LED signal
Y21
Overflow occurrence confirmation LED signal
QY10 (Y20 to Y2F)
X0 Module
ready
X2
Counter value coincidence (point No. 1)
Y0
Coincidence signal No. 1 reset command
Y1 Preset
command
Y2
Coincidence signal enable command
Y4
Count enable command
Y6
Counter function selection start command
QD62(E/D) (X/Y0 to X/YF)
8
Summary of Contents for QD62
Page 1: ......
Page 2: ......
Page 13: ...A 11 A 11 MEMO ...
Page 55: ...4 18 4 18 MELSEC Q 4 SETUP AND PROCEDURE BEFORE STARTING THE OPERATION MEMO ...
Page 97: ...8 5 8 5 MELSEC Q 8 PROGRAMMING 3 Program example a Set only when the linear counter is used ...
Page 100: ...8 8 8 8 MELSEC Q 8 PROGRAMMING 2 Program example a Set only when the ring counter is used ...
Page 127: ......
Page 128: ......