VII
Control ]
- 12
6
-
HWE0713A
GB
(3) Outdoor unit heat exchanger capacity control patterns
Model
Operation
mode
Operation
patterns
Solenoid valve
SV4a
SV4b
SV4c
SV4d
SV5c
P2
5
0 - P300 and
EP200 models
Cooling-
only
Cooling-
main
1
OFF
OFF
-
ON
ON
2
OFF
OFF
-
OFF
ON
3
OFF
ON
-
OFF
ON
4
ON
OFF
-
OFF
ON
5
ON
ON
-
OFF
OFF
Heating-
only
1
ON
ON
-
OFF
OFF
Heating-
main
1
ON
ON
-
ON
OFF
2
ON
ON
-
OFF
OFF
Defrost
1
ON
ON
-
OFF
OFF
P350 - P400 and
EP250 - EP300
models
Cooling-
only
Cooling-
main
1
OFF
OFF
OFF
ON
ON
2
OFF
OFF
OFF
OFF
ON
3
OFF
OFF
ON
OFF
ON
4
OFF
ON
ON
OFF
ON
5
ON
ON
ON
OFF
OFF
Heating-
only
1
ON
ON
ON
OFF
OFF
Heating-
main
1
ON
ON
ON
ON
OFF
2
ON
ON
ON
OFF
OFF
Defrost
1
ON
ON
ON
OFF
OFF
Summary of Contents for PURY-(E)P200
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 63: ... II Restrictions 54 HWE0713A GB ...
Page 65: ... 56 ...
Page 81: ... 72 III Outdoor Unit Components GB HWE0713A ...
Page 83: ... 74 ...
Page 91: ... 82 IV Remote Controller GB HWE0713A ...
Page 93: ... 84 ...
Page 105: ... 96 ...
Page 121: ... 112 VI Refrigerant Circuit GB HWE0713A ...
Page 123: ... 114 ...
Page 151: ... 142 ...
Page 195: ... 186 ...
Page 315: ... 306 IX Troubleshooting GB HWE0713A ...
Page 317: ... 308 ...