II
Restrictions ]
- 43 -
HWE0713A
GB
[8] Restrictions on Pipe Length
(1) System that requires 16 BC controller ports or fewer <System with only the main BC controller or standard BC con-
troller>
1) Do not connect the P200 or P250 models of indoor units and other models of indoor units at the same port.
2) All the units that are connected to the same ports can only be operated in the same operation mode (cooling/heating).
a
b
H H'
h1
A
h2
Outdoor unit
BC controller
Reducer (P15 - P50 models)
(Supplied with the BC Controller)
B
d
c
Junction pipe
(CMY-R160-J)
*Use a main BC controller when connecting the outdoor units of
(E)P400 model or above.
Branch joint
(CMY-Y102S-G2)
Indoor
Indoor
Indoor
Indoor
(P15 - P140 models)
(P200 - P250 models)
Maximum of 3 units per port
Total capacity of P80 or below
Unit: m [ft]
Operation
Pipe sections
Allowable length of pipes
Length
Total pipe length
A+B+a+b+c+d
Refer to the restrictions on the total piping
length in the graph on the next page.
Total pipe length from the outdoor unit
to the farthest indoor unit
A+B+d
165 [541] or less
(Equivalent length 190 [623] or less)
Between outdoor unit and BC control-
ler
A
110 [360] or less
Between BC controller and indoor unit
B+d
40 [131] or less
*1
Height
difference Between indoor
and outdoor units
Outdoor unit
above indoor unit
H
50 [164] or less
Outdoor unit be-
low indoor unit
H'
40 [131] or less
Between indoor unit and BC controller
h1
15[49](10[32]) or less
*2
Between indoor units
h2
15[49](10[32]) or less
*2
*1. When the overall pipe length between the BC controller and the farthest indoor unit exceeds 40m [131ft], observe the
restrictions in the figure titled "Restrictions on pipe length" below. (Except the P250 models)
*2. When the capacity of the connected indoor units is P200 or above, use the figures in the parentheses as a reference.
Summary of Contents for PURY-(E)P200
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 63: ... II Restrictions 54 HWE0713A GB ...
Page 65: ... 56 ...
Page 81: ... 72 III Outdoor Unit Components GB HWE0713A ...
Page 83: ... 74 ...
Page 91: ... 82 IV Remote Controller GB HWE0713A ...
Page 93: ... 84 ...
Page 105: ... 96 ...
Page 121: ... 112 VI Refrigerant Circuit GB HWE0713A ...
Page 123: ... 114 ...
Page 151: ... 142 ...
Page 195: ... 186 ...
Page 315: ... 306 IX Troubleshooting GB HWE0713A ...
Page 317: ... 308 ...