IX
Troubleshooting ]
- 24
5
-
HWE0713A
GB
In the case of MA remote controller
2. Phenomena
When the remote controller operation SW is turned on, the operation status briefly appears on the display, then it goes off,
and the display lights out immediately, and the unit stops.
(1) Cause
1) The power for the M-NET transmission line is not supplied from the outdoor unit.
2) Short circuit of the transmission line.
3) Incorrect wiring of the M-NETtransmission line on the outdoorunit.
Disconnected wire for the MA remote controller or disconnected line to the terminal block.
The indoor transmission line is connected incorrectly to the transmission terminal block for centralized controller (TB7).
The male power supply connectors on the multiple outdoor units are connected to the female power supply switch connector
(CN40).
In the system to which the power supply unit for transmission lines is connected, the male power supply connector is connect-
ed to the female power supply switch connector (CN40) on the outdoor unit.
4) Disconnected M-NET transmission line on the indoor unit side.
5) Disconnected wire between the terminal block for M-NET line (TB5) of the indoor unit and the indoor unit board (CN2M) or
disconnected connector.
(2) Check method and remedy
1)
When 2) and 3) above apply, check code 7102 will be displayed on the self-diagnosis LED.
Refer to IX [4] -8- (2) "Troubleshooting transmission power circuit of outdoor unit" for how to check item 1 in the flow chart
above.
YES
YES
YES
YES
NO
NO
NO
NO
Same symptom for all units in a
system with one outdoor unit?
Check the
self-diagnosis LED
Check 1).
Check for
2 and 3.
Check 4.
Measure voltages of the
terminal block for transmission
line (TB5) on the indoor unit.
17 - 30V?
Check 5.
Error found?
Indoor unit board or
MA remote controller failure
Correct
the error.
Correct the error.
Is the error code 7102
displayed?
Summary of Contents for PURY-(E)P200
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 63: ... II Restrictions 54 HWE0713A GB ...
Page 65: ... 56 ...
Page 81: ... 72 III Outdoor Unit Components GB HWE0713A ...
Page 83: ... 74 ...
Page 91: ... 82 IV Remote Controller GB HWE0713A ...
Page 93: ... 84 ...
Page 105: ... 96 ...
Page 121: ... 112 VI Refrigerant Circuit GB HWE0713A ...
Page 123: ... 114 ...
Page 151: ... 142 ...
Page 195: ... 186 ...
Page 315: ... 306 IX Troubleshooting GB HWE0713A ...
Page 317: ... 308 ...