IX
Troubleshooting ]
- 2
09
-
HWE0713A
GB
1. Error
Code
ACCT overcurrent (H/W detection) (Detail code 102)
DCCT overcurrent (H/W detection) (Detail code 103)
Instantaneous overcurrent (Detail code 106)
Overcurrent (Detail code 107)
2. Error definition and error detection method
Overcurrent 94Apeak or 22Arm and above is detected (P250, EP200 models) OR 94Apeak or 35Arm and above is de-
tected (P300-P400, EP250-EP300 model and above) by the current sensor.
3. Cause, check method and remedy
Refer to section -7- "Inverter" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 283)
1. Error
Code
Short-circuited IPM/Ground fault (Detail code 104)
2. Error definition and error detection method
When IPM/IGBT short damage or grounding on the load side is detected just before starting the inverter.
3. Cause, check method and remedy
In the case of 4250
In the case of 4255
Refer to section -7- "Inverter" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 283)
4250
Cause
Check method and remedy
(1)
Inverter output related
Refer to IX [4] -7- (2) [1]-[4]. (page 285)
Check the IGBT module resistance value of the in-
verter board, if no problems are found.
(Refer to the Trouble shooting for IGBT module)
4250
4255
Cause
Check method and remedy
(1)
Grounding fault compressor
Refer to IX [4] -7- (2) [2].(page 285)
(2)
Inverter output related
Refer to IX [4] -7- (2) [1]-[4].(page 285)
Cause
Check method and remedy
(1)
Grounding fault of fan motor
Refer to IX [4] -7- (2) [5].(page 286)
(2)
Fan board failure
Refer to IX [4] -7- (2) [6].(page 287)
Summary of Contents for PURY-(E)P200
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 63: ... II Restrictions 54 HWE0713A GB ...
Page 65: ... 56 ...
Page 81: ... 72 III Outdoor Unit Components GB HWE0713A ...
Page 83: ... 74 ...
Page 91: ... 82 IV Remote Controller GB HWE0713A ...
Page 93: ... 84 ...
Page 105: ... 96 ...
Page 121: ... 112 VI Refrigerant Circuit GB HWE0713A ...
Page 123: ... 114 ...
Page 151: ... 142 ...
Page 195: ... 186 ...
Page 315: ... 306 IX Troubleshooting GB HWE0713A ...
Page 317: ... 308 ...