II
Restrictions ]
- 50 -
HWE0713A
GB
2. Connecting the BC controller
(1) Size of the pipe that fits the standard BC controller ports
(E)P200 - P350 models
* BC controllers can only be connected to (E)P200 - P350 models of outdoor units.
Unit : mm [inch]
Operation
Pipe sections
High-pressure side (liquid)
Low-pressure side (gas)
Outdoor unit side
PURY-EP200YHM-A
ø15.88 [5/8"]
(Brazed connection)
ø19.05 [3/4"]
(Brazed connection)
PURY-(E)P250YHM-A
PURY-(E)P300YHM-A
ø19.05 [3/4"]
(Brazed connection)
ø22.2 [7/8"]
(Brazed connection)
PURY-P350YHM-A
ø28.58 [1-1/8"]
(Brazed connection)
Indoor unit side
ø9.52 [3/8"] (Flare connection)
ø15.88 [5/8"]
(Flare connection)
Indoor
Indoor
Indoor
Indoor
Indoor
Indoor
BC controller
Maximum of 3 units per port
Total capacity of P80 or below
(All units connected to the same port
must be in the same operating mode.)
Branch joint (Model name:CMY-Y102S-G2)
(Optional accessory)
*2
Junction pipe kit
(Model name:
CMY-R160-J)
(Optional accessory)
P50 model or below P63-P140 models P200-P250 models
The ports of the BC controller accommodates the pipes on P63-P140 models of indoor units.
To connect other types of indoor units, follow the procedure below.
3*
A
B
*1
Reducer
(Standard
supplied parts)
To outdoor unit
Connection: Brazed connection
Summary of Contents for PURY-(E)P200
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 63: ... II Restrictions 54 HWE0713A GB ...
Page 65: ... 56 ...
Page 81: ... 72 III Outdoor Unit Components GB HWE0713A ...
Page 83: ... 74 ...
Page 91: ... 82 IV Remote Controller GB HWE0713A ...
Page 93: ... 84 ...
Page 105: ... 96 ...
Page 121: ... 112 VI Refrigerant Circuit GB HWE0713A ...
Page 123: ... 114 ...
Page 151: ... 142 ...
Page 195: ... 186 ...
Page 315: ... 306 IX Troubleshooting GB HWE0713A ...
Page 317: ... 308 ...