-7- Defrost Operation Control
(1) Starting the defrost operation
The defrost cycle starts when the pipe temperature (TH6), in the following table, or below has continuously been detected for
3 minutes after the integrated compressor operation time of 50 minutes have passed (90 minutes when the defrost prohibit
timer is set to 90 minutes).
If 10 minutes have passed since compressor start-up or since the completion of defrost operation, forced defrost operation
will start by turning on the forced defrost switch (DIP SW2-7).
Even if the defrost prohibit timer is set to 90 minutes, the actual defrost prohibit time for the next operation will be 50 minutes
if defrosting took 12 minutes.
In the multiple-outdoor-unit system, all of the outdoor units that are in operation go into the defrost mode simultaneously. The
unit(s) that is stopped at the time defrost operation starts remains stopped.
(2) Defrost operation
Model
TH6
SW3 - 3 OFF
SW3 - 3 ON
P250 model
- 10°C [14°F]
- 5°C [23°F]
P300 model
- 10°C [14°F]
- 5°C [23°F]
P350 model
- 8°C [18°F]
- 5°C [23°F]
P400 model
- 8°C [18°F]
- 5°C [23°F]
EP200 model
- 10°C [14°F]
- 5°C [23°F]
EP250 model
- 8°C [18°F]
- 5°C [23°F]
EP300 model
- 8°C [18°F]
- 5°C [23°F]
Outdoou unit
Compressor frequency
Model
Compressor frequency
P250 model
65 Hz
P300 model
65 Hz
P350 model
103 Hz
P400 model
103 Hz
EP200 model
65 Hz
EP250 model
103 Hz
EP300 model
103 Hz
Outdoor unit fan
Stopped
SV1a
ON (open)
SV2
ON (open)
SV5b
ON (open)
F
F
O
a
4
S
1
2
SV9
OFF (closed)
BC controller
LEV1
G type: 4000, GA type: 6000, HA type: 8000
LEV3
G type: 1000, GA type: 2000, HA type: 2000
GB, HB type: 60 (full closed)
SVM1
ON
SVM2
OFF
SVM1b
ON
SVM2b
OFF
SV B
OFF
SV A
Ports that are connected to the indoor units in cooling Thermo-ON
Other ports : OFF
Summary of Contents for PURY-(E)P200
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 63: ... II Restrictions 54 HWE0713A GB ...
Page 65: ... 56 ...
Page 81: ... 72 III Outdoor Unit Components GB HWE0713A ...
Page 83: ... 74 ...
Page 91: ... 82 IV Remote Controller GB HWE0713A ...
Page 93: ... 84 ...
Page 105: ... 96 ...
Page 121: ... 112 VI Refrigerant Circuit GB HWE0713A ...
Page 123: ... 114 ...
Page 151: ... 142 ...
Page 195: ... 186 ...
Page 315: ... 306 IX Troubleshooting GB HWE0713A ...
Page 317: ... 308 ...