
[
VIII
Test Run Mode ]
- 1
-
HWE0713A
GB
Operation
Outdoor unit model
PURY-P600YSHM-A
PURY-P300YHM-A
PURY-P300YHM-A
Model name of BC controller
CMB-P108V-GA
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
27°C/19°C [81°F/66°F]
Outdoor
35°C/- [95°F/-]
Indoor unit
No. of connected units
Unit
6
No. of units in operation
6
Model
-
56/112/112/112/140/140
Piping
Main pipe
m
[ft]
5 [16-3/8"]
Branch pipe
10 [32-3/4"]
Total pipe length
65 [213-1/4"]
Fan speed
-
Hi
Amount of refrigerant
kg
[lbs-oz]
37.2 [83]
Outdoor
unit
Electric current
A
31.4
Voltage
V
400
Compressor frequency
Hz
74
74
LEV open-
ing
Indoor unit
Pulse
362/325/325/325/387/387
BC controller (1/2/3)
2000/2000/240
Pressure
High pressure(63HS1)/
Low pressure(63LS)
MPa
[psi]
3.12/0.86
[453/125]
3.12/0.86
[453/125]
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
2.93/2.93
[425/425]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C
[°F]
86 [187]
86 [187]
Heat exchanger outlet
(TH3)
41 [106]
41 [106]
Accumulator inlet
8 [46]
8 [46]
Accumulator outlet
8 [46]
8 [46]
Compressor inlet
19 [66]
19 [66]
Compressor shell bottom
42 [108]
42 [108]
Indoor unit
LEV inlet
19 [66]
Heat exchanger outlet
6 [43]
Summary of Contents for PURY-(E)P200
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 63: ... II Restrictions 54 HWE0713A GB ...
Page 65: ... 56 ...
Page 81: ... 72 III Outdoor Unit Components GB HWE0713A ...
Page 83: ... 74 ...
Page 91: ... 82 IV Remote Controller GB HWE0713A ...
Page 93: ... 84 ...
Page 105: ... 96 ...
Page 121: ... 112 VI Refrigerant Circuit GB HWE0713A ...
Page 123: ... 114 ...
Page 151: ... 142 ...
Page 195: ... 186 ...
Page 315: ... 306 IX Troubleshooting GB HWE0713A ...
Page 317: ... 308 ...