VIII
Test Run Mode ]
- 15
-
HWE0713A
GB
Operation
Outdoor unit model
PURY-P400YHM-A
Model name of BC controller
CMB-P104V-G
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
20°C/-
[68°F/-]
Outdoor
7°C/6°C
[45°F/43°F]
Indoor unit
No. of connected units
Unit
4
No. of units in operation
4
Model
-
112/112/112/112
Piping
Main pipe
m
[ft]
5 [16-3/8"]
Branch pipe
10 [32-3/4"]
Total pipe length
45 [147-5/8"]
Fan speed
-
Hi
Amount of refrigerant
kg
[lbs-oz]
24.4 [54]
Outdoor
unit
Electric current
A
21.9
Voltage
V
400
Compressor frequency
Hz
102
LEV open-
ing
Indoor unit
Pulse
332/332/332/332
BC controller (1/2/3)
110/110/800
Pressure
High pressure(63HS1)/
Low pressure(63LS)
MPa
[psi]
2.68/0.56
[389/81]
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
2.64/2.32
[383/336]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C
[°F]
82 [180]
Heat exchanger outlet
(TH6)
1 [34]
Accumulator inlet
-4 [25]
Accumulator outlet
-4 [25]
Compressor inlet
-4 [25]
Compressor shell bottom
40 [104]
Indoor unit
LEV inlet
37 [99]
Heat exchanger outlet
70 [158]
Summary of Contents for PURY-(E)P200
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 63: ... II Restrictions 54 HWE0713A GB ...
Page 65: ... 56 ...
Page 81: ... 72 III Outdoor Unit Components GB HWE0713A ...
Page 83: ... 74 ...
Page 91: ... 82 IV Remote Controller GB HWE0713A ...
Page 93: ... 84 ...
Page 105: ... 96 ...
Page 121: ... 112 VI Refrigerant Circuit GB HWE0713A ...
Page 123: ... 114 ...
Page 151: ... 142 ...
Page 195: ... 186 ...
Page 315: ... 306 IX Troubleshooting GB HWE0713A ...
Page 317: ... 308 ...