[
VIII
Test Run Mode ]
- 133 -
HWE10130
GB
(2) Heating operation
Operation
Outdoor unit model
PUHY-RP400YSJM-B
PUHY-RP200YJM-B
PUHY-RP200YJM-B
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
20°C/- [68°F/- ]
Outdoor
7°C/6°C
[45°F/43°F]
Indoor
unit
No. of connected
units
Unit
4
No. of units in opera-
tion
4
Model
-
200/100/63/32
Piping
Main pipe
m [ ft ]
10 [32-3/4]
Branch pipe
5 [16-3/8]
Total pipe length
30 [98]
Fan speed
-
Hi
Amount of refrigerant
kg
[ lbs-oz ]
20.6 [46]
Outdoor
unit
Electric current
A
18.4
Voltage
V
400
Compressor frequency
Hz
54
54
LEV open-
ing
Indoor unit
Pulse
315/315/432/241
SC (LEV1)
-
-
LEV2
-
-
Pressure
High pressure (after O/S)/low
pressure (before accumulator)
MPa
[ psi ]
2.60/0.72
2.60/0.72
[377/104]
[377/104]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C [ °F ]
73 [163]
73 [163]
Heat exchanger out-
let (TH3)
12 [54]
12 [54]
Accumulator inlet
1 [34]
1 [34]
Accumulator outlet
3 [37]
3 [37]
Compressor inlet
3 [37]
3 [37]
Compressor shell
bottom
22 [72]
22 [72]
Indoor
unit
LEV inlet
33 [91]
33 [91]
Heat exchanger
outlet
61 [142]
61 [142]
Summary of Contents for PUHY-RP200
Page 9: ...HWE10130 GB ...
Page 11: ... 2 ...
Page 21: ... 12 I Read Before Servicing GB HWE10130 ...
Page 23: ... 14 ...
Page 63: ... 54 II Restrictions GB HWE10130 ...
Page 65: ... 56 ...
Page 75: ... 66 ...
Page 83: ... 74 IV Remote Controller GB HWE10130 ...
Page 85: ... 76 ...
Page 89: ... 80 ...
Page 95: ... VI Refrigerant Circuit 86 HWE10130 GB ...
Page 97: ... 88 ...
Page 121: ... 112 VII Control GB HWE10130 ...
Page 123: ... 114 ...
Page 159: ... 150 ...
Page 259: ... 250 IX Troubleshooting GB HWE10130 ...
Page 261: ... 252 ...