II
Restrictions ]
- 15 -
HWE10130
GB
II
Restrictions
[1] System configuration
1. Table of compatible indoor units
The table below summarizes the types of indoor units that are compatible with different types of outdoor units.
(1) Standard combinations
1) "Maximum total capacity of connectable indoor units" refers to the sum of the numeric values in the indoor unit model names.
2) If the total capacity of the indoor units that are connected to a given outdoor unit exceeds the capacity of the outdoor unit, the
indoor units will not be able to perform at the rated capacity when they are operated simultaneously. Select a combination of
units so that the total capacity of the connected indoor units is at or below the capacity of the outdoor unit whenever possible.
Outdoor
units
Composing units
Maximum total capacity
of connectable indoor
units
Maximum number
of connectable in-
door units
Types of connectable in-
door units
200
-
-
-
100 - 260
17
P15 - P250 models
R410A series indoor units
250
-
-
-
125 - 325
21
300
-
-
-
150 - 390
26
350
-
-
-
175 - 455
30
400
200
200
-
200 - 520
32
450
200
250
-
225 - 585
32
500
250
250
-
250 - 650
32
550
250
300
-
275 - 715
32
600
300
300
-
300 - 780
32
650
300
350
-
325 - 845
32
700
200
250
250
350 - 910
32
750
250
250
250
375 - 975
32
800
250
250
300
400 - 1040
32
850
250
300
300
425 - 1105
32
900
300
300
300
450 - 1170
32
Summary of Contents for PUHY-RP200
Page 9: ...HWE10130 GB ...
Page 11: ... 2 ...
Page 21: ... 12 I Read Before Servicing GB HWE10130 ...
Page 23: ... 14 ...
Page 63: ... 54 II Restrictions GB HWE10130 ...
Page 65: ... 56 ...
Page 75: ... 66 ...
Page 83: ... 74 IV Remote Controller GB HWE10130 ...
Page 85: ... 76 ...
Page 89: ... 80 ...
Page 95: ... VI Refrigerant Circuit 86 HWE10130 GB ...
Page 97: ... 88 ...
Page 121: ... 112 VII Control GB HWE10130 ...
Page 123: ... 114 ...
Page 159: ... 150 ...
Page 259: ... 250 IX Troubleshooting GB HWE10130 ...
Page 261: ... 252 ...